0063010 ват

Watts 009M2 Reduced Pressure Zone Backflow Preventer (Model 0063010) Instruction Manual

For Models: 009M2, 009M2-QT

1. Уводзіны

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. Важная інфармацыя па бяспецы

  • Прапанова 65 Папярэджанне: Гэты прадукт можа ўтрымліваць хімічныя рэчывы, вядомыя штату Каліфорнія, якія выклікаюць рак і прыроджаныя дэфекты альбо іншую шкоду рэпрадукцыі.
  • Non-Potable Use Only: This device does not conform to the Lead-Free Act. It is intended for non-potable water applications only, such as irrigation systems or fire sprinkler systems. DO NOT USE FOR DRINKING WATER.
  • Installation must be performed by a qualified professional in accordance with all national and local plumbing codes and water authority requirements.
  • Ensure the water supply is shut off and depressurized before attempting any installation or maintenance.
  • Карыстайцеся адпаведнымі сродкамі індывідуальнай абароны (СІА) падчас усталёўкі і тэхнічнага абслугоўвання.
  • Regular testing and maintenance are essential to ensure the continued proper function of the backflow preventer.

3. Прадукт скончыўсяview і кампаненты

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

  • Bronze Body: Забяспечвае даўгавечнасць і ўстойлівасць да карозіі.
  • Quarter-Turn Ball Valve Shutoffs: Resilient seated with tee handles for easy operation.
  • Top-Mounted Test Cocks: Screwdriver slotted for convenient testing.
  • In-line Independent Check Valves: Two check valves for reliable backflow prevention.
  • Captured Springs: For safe maintenance procedures.
  • Replaceable Check Seats: Allows for economical repair and extended product life.
  • Internal Relief Valve: Reduces installation clearances.
  • Single Access Cover: Facilitates easy in-line repairs.
Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. Настройка і ўстаноўка

  1. Праверка перад устаноўкай:
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • Inspect the unit for any shipping damage.
    • Ensure all necessary tools and materials for installation are available.
  2. Падрыхтоўка пляцоўкі:
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. Злучэнне трубаправодаў:
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. Праверка пасля ўстаноўкі:
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • Агледзіце ўсе злучэнні на герметычнасць.
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. Інструкцыя па эксплуатацыі

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

  • Shutoff Valves: The quarter-turn ball valve shutoffs (with tee handles) are used to isolate the backflow preventer for maintenance or testing.
    • To open: Turn the handle parallel to the pipe.
    • To close: Turn the handle perpendicular to the pipe.
    • Always operate these valves slowly to prevent water hammer.
  • Test Cocks: The top-mounted test cocks are used by certified backflow prevention testers to verify the proper function of the check valves and relief valve. These should only be operated by qualified personnel during testing procedures.

6. Тэхнічнае абслугоўванне

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

  • Штогадовае тэставанне: The backflow preventer must be tested annually, or more frequently as required by local codes, by a certified backflow prevention tester.
  • Servicing Check Valves and Relief Valve:
    • Isolate the unit by closing both upstream and downstream shutoff valves.
    • Depressurize the unit by opening the test cocks.
    • Remove the single access cover to access the internal components.
    • The check valves and relief valve feature captured springs for safe disassembly.
    • Replaceable check seats allow for economical repair. Consult the Watts service manual or a qualified technician for detailed disassembly and reassembly procedures.
    • No special tools are required for servicing the internal components.
  • Уборка: Periodically inspect and clean internal components to remove any debris or mineral deposits that could impede proper function.
  • Зімоўка: In climates where freezing temperatures are a concern, the backflow preventer must be properly drained or protected from freezing to prevent damage.

7. Выпраўленне непаладак

праблемаМагчымая прычынаРашэнне
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
Няма патоку вады або паніжаны паток
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Ensure shutoff valves are fully open.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
Уцечкі з злучэнняў
  • Improperly sealed threads
  • Damaged gaskets
  • Re-apply thread sealant and tighten connections.
  • Inspect and replace gaskets.

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. Тэхнічныя характарыстыкі

Нумар мадэлі0063010 (009M2)
Backflow Preventer TypeЗборка зоны паніжанага ціску
Матэрыял корпусаБронза
Inlet/Outlet Connection Size2 Inches (50 MM)
Inlet/Outlet Connection TypeFemale Threaded NPT
Максімальны працоўны ціск175 PSI (12.10 BAR)
Максімальная тэмпература180°F (82°C)
Мінімальная тэмпература33°F (0.5°C)
Тып абароныBackpressure and Backsiphonage
Памеры прадукту (Д х Ш х У)22 х 10 х 8 цалі
Вага прадмета27 фунта
Lead Free StatusNO (For non-potable use only)

9. Гарантыя і падтрымка

Specific warranty information for Watts products is typically provided with the product packaging or available on the official Watts website. Please refer to these resources for the most current warranty terms and conditions.

For technical support, replacement parts, or further assistance, please contact Watts customer service or visit their official website. Ensure you have your product model number (0063010) and serial number (if applicable) ready when contacting support.

Watts Official Webсайт: www.watts.com