U.S. Solid USS-MSV00072

U.S. Solid Motorized Ball Valve Instruction Manual

Model: USS-MSV00072 | 3/4" Stainless Steel, 9-24V AC/DC, 2-Wire Auto Return

1. Уводзіны

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your U.S. Solid Motorized Ball Valve. Please read these instructions thoroughly before installation and retain this manual for future reference. This valve is designed for various applications requiring automated fluid control, featuring a durable stainless steel construction and a 2-wire auto return setup.

2. Інфармацыя па бяспецы

  • Always disconnect power before installing, servicing, or performing any maintenance on the valve.
  • Пераканайцеся, што ўсе электрычныя падключэнні адпавядаюць мясцовым нормам і правілам.
  • Карыстайцеся адпаведнымі сродкамі індывідуальнай абароны (СІА) падчас усталёўкі і тэхнічнага абслугоўвання.
  • Праверце тtage supply matches the valve's specifications (9-24V AC/DC).
  • Do not exceed the maximum operating pressure of 10 bars (145 PSI).
  • Avoid installing the valve in locations subject to extreme temperatures or corrosive environments beyond its IP65 rating.

3. Прадукт скончыўсяview

3.1 Асноўныя магчымасці

  • матэрыял: Constructed from 304 stainless steel for durability and reliability.
  • Памер порта: 3/4" NPT threading with a full port design to minimize pressure loss.
  • тtage: Operates on 9-24V AC/DC.
  • Аперацыя: Opens or closes in 3-5 seconds.
  • Праводка: Simple 2-wire automatic return setup.
  • Бяспека: Limit switch minimizes power consumption once fully open or closed, reducing overheating risk.
  • Абарона: IP65 rated for dust-tight and water jet protection.

3.2 Кампаненты

The U.S. Solid Motorized Ball Valve consists of two primary components: the stainless steel ball valve body and the motorized actuator unit. The actuator houses the motor, gearing, and control electronics.

Фронт view of the U.S. Solid Motorized Ball Valve

Малюнак 1: Спераду view of the U.S. Solid Motorized Ball Valve, showing the blue actuator and stainless steel valve body.

Збоку view of the U.S. Solid Motorized Ball Valve

Малюнак 2: бок view of the valve, illustrating the compact design of the actuator and the threaded valve connections.

Internal circuit board of the motorized actuator

Малюнак 3: Унутраны view of the actuator's circuit board, showing electronic components and wiring connections.

3.3 Тэхнічныя характарыстыкі

Dimensions of the U.S. Solid Motorized Ball Valve

Figure 4: Product dimensions, showing approximate measurements of the valve and actuator assembly.

СпецыфікацыяКаштоўнасць
Нумар мадэліUSS-MSV00072
МатэрыялНержавеючая сталь (304)
Памер0.75 Inch (3/4")
Inlet/Outlet Connection Size3/4 цаляў
Inlet/Outlet Connection TypeНацыянальны канічны дыяметр трубы (NPT)
тtage9-24V AC / DC
Максімальны працоўны ціск10 бар (145 фунтаў на квадратны дюйм)
Колькасць партоў2
Час спрацоўвання3-5 секунды
Працягласць жыцця80,000 to 100,000 cycles
Рэйтынг абароныIP65
Вага прадмета12.7 унцыі
Памеры прадукту (Д х Ш х У)3.66 х 2.68 х 2.48 цалі
IP65 Ingress Protection Rating Chart

Figure 5: Explanation of the IP65 ingress protection rating, indicating dust-tightness and protection against water jets.

4. Настройка і ўстаноўка

4.1 Механічны мантаж

  1. Перад устаноўкай пераканайцеся, што сістэма не пад ціскам і не мае вады.
  2. Apply PTFE (Teflon) tape to the male pipe threads to ensure a watertight seal. Wrap the tape clockwise around the threads, typically 3-5 layers.
  3. Applying Teflon tape to pipe threads

    Figure 6: Illustration of applying Teflon tape to male pipe threads for a secure, leak-free connection.

  4. Screw the valve firmly into the piping system. Do not overtighten, as this can damage the threads or valve body.
  5. Ensure the valve is installed in an accessible location for future maintenance.

4.2 Electrical Wiring (2-Wire Auto Return Setup)

This valve features a 2-wire auto return setup, meaning it will return to its fully open position if power is removed. It is a Normally Open (NO) valve, which means it is open when no power is applied.

  • For DC Power: Connect the red wire to the positive (+) terminal and the black wire to the negative (-) terminal of your 9-24V DC power supply. Applying power will close the valve. Removing power will cause the valve to automatically return to its open position.
  • For AC Power: Connect the red wire to one AC line and the black wire to the other AC line of your 9-24V AC power supply. Applying power will close the valve. Removing power will cause the valve to automatically return to its open position.
2-Wire Auto Return Wiring Diagram for DC and AC

Figure 7: Wiring diagram for the 2-wire auto return setup, illustrating connections for both DC and AC power sources.

5. Аперацыя

The U.S. Solid Motorized Ball Valve is designed for simple on/off control. As a Normally Open (NO) valve, its default state without power is open.

  • Каб закрыць клапан: Apply 9-24V AC/DC power to the red and black wires. The actuator will rotate, closing the ball valve. Once fully closed, an internal limit switch will cut power to the motor, preventing overheating.
  • Каб адкрыць клапан: Remove the 9-24V AC/DC power from the red and black wires. The actuator will automatically return to its original position, opening the ball valve.
Normally Open Valve Operation Diagram

Figure 8: Diagram illustrating the 'Normally Open' operation, showing the valve's state with and without power.

6. Тэхнічнае абслугоўванне

The U.S. Solid Motorized Ball Valve is designed for minimal maintenance. Regular inspection can help ensure long-term reliable operation.

  • Перыядычная праверка: Visually inspect the valve and actuator for any signs of damage, corrosion, or leaks. Check electrical connections for tightness and integrity.
  • Уборка: If necessary, clean the exterior of the valve and actuator with a damp cloth. Do not use harsh chemicals or abrasive cleaners. Ensure no water enters the actuator housing.
  • Праверка прывада: Periodically cycle the valve (open and close) to ensure smooth operation. Listen for any unusual noises during actuation.

7. Выпраўленне непаладак

If you encounter issues with your motorized ball valve, refer to the following troubleshooting guide:

праблемаМагчымая прычынаРашэнне
Valve does not actuate (open/close)Няма харчавання або няправільны аб'ёмtage
Няшчыльнае злучэнне правадоў
Няспраўнасць рухавіка
Verify power supply (9-24V AC/DC) and connections.
Check for secure wiring. Ensure correct polarity for DC.
If power is present and connections are secure, the motor may be faulty. Contact support.
Valve does not fully open or closeЗакаркаванне ў клапане
Недастатковая магутнасць
Internal gear damage (as noted in some user experiences)
Inspect the valve for debris. Ensure adequate power supply.
If the issue persists, the internal mechanism may be damaged. Contact support.
Уцечка клапанаImproperly sealed threads
Damaged valve body or seals
Ensure PTFE tape was applied correctly and connections are tight.
If the leak is from the valve body itself, the valve may be damaged and require replacement.
Прывад выдае незвычайны гукInternal gear wear or damageThis may indicate internal wear. Monitor operation; if performance degrades, consider replacement.

8. Гарантыя і падтрымка

U.S. Solid offers a 1-year warranty or money-back promise on its products, ensuring customer satisfaction. For technical support, warranty claims, or further assistance, please visit the official U.S. Solid store or contact their customer service department.

U.S. Solid Store: https://www.amazon.com/stores/USSolid/page/29AB675D-2238-4826-BDE2-09EFEAB81AA6

Ask a question about this manual