GEYA 3P-63A-110VAC

GEYA Mini ATS Automatic/Manual Transfer Switch User Manual

Model: 3P-63A-110VAC

Марка: GEYA

1. Уводзіны

This manual provides detailed instructions for the installation, operation, and maintenance of the GEYA Mini ATS Automatic/Manual Transfer Switch, Model 3P-63A-110VAC. This device is designed to automatically or manually switch between two power sources, such as grid power, a generator, or a photovoltaic system, ensuring continuous power supply to your load.

GEYA Mini ATS Automatic/Manual Transfer Switch

Figure 1: GEYA Mini ATS Automatic/Manual Transfer Switch (Model 3P-63A-110VAC)

2. Інфармацыя па бяспецы

Please read and understand all safety warnings and instructions before installing or operating this device. Failure to follow these instructions may result in electric shock, fire, or serious injury.

  • Усталёўку і абслугоўванне павінны выконваць толькі кваліфікаваныя спецыялісты.
  • Always disconnect all power sources before working on the switch or connected circuits.
  • Забяспечце належнае зазямленне, каб прадухіліць паражэнне электрычным токам.
  • Праверыць выпtagЭлектрычнасць і намінальны ток перамыкача адпавядаюць патрабаванням вашага прымянення.
  • Не выкарыстоўвайце выключальнік у вільготным абоamp умовы.
  • Выпtage of the common and backup power supply must be 85-110% of the rated voltage.
  • The current cannot be less than 5A, otherwise the coil may overheat or combust.
  • The backup power of the product must be a stable city power, otherwise the product will not switch automatically.

3. Асаблівасці прадукту

  • Сумяшчальнасць з двума крыніцамі харчавання: Designed for automatic or manual conversion between two power supplies (e.g., mains, generator, photovoltaic).
  • Над-тtagе і пад-выпtage Protection (110V/50Hz):
    • Undervoltage value: 85V, Recovery value: 95V (± 5V)
    • Аверволtage value: 145V, Recovery value: 130V (± 5V)
  • Над-тtagе і пад-выпtage Protection (220V/50Hz):
    • Undervoltage value: 175V, Recovery value: 195V (± 5V)
    • Аверволtage value: 260V, Recovery value: 240V (± 5V)
  • Аўтаматычнае пераключэнне: When the normal power supply is abnormal, the device automatically switches to the backup power supply. It switches back to normal power when restored.
  • Светавыя індыкатары: Equipped with indicator lights for both power sources (A and B) to show operational status.
  • Fast Switching: Power switch completed within 100 milliseconds, minimizing power interruptions.
  • Інтэлектуальнае кіраванне: Features self-restoring, over-voltagе, і пад-тtagэлектронная абарона.
  • Трывалая канструкцыя: Utilizes silver contacts and copper terminals for reliability and longevity.
  • Мантаж на DIN-рэйку: Compatible with universal DIN rail mounting for easy installation.
Function of Automatic Transfer Switch

Figure 2: Explanation of Automatic Transfer Switch Function

Fast Switching and Intelligent Control Features

Figure 3: Fast Switching and Intelligent Control Capabilities

Silver Contacts, Copper Terminals, and Guide Rail Installation

Figure 4: Internal Components and Installation Method

4. How to Choose Your Model

Refer to the table below to select the appropriate ATS model based on your live line voltage and connection requirements.

Model Selection Guide for GEYA ATS

Figure 5: Model Selection Guide

Model Selection Table
Live Line VoltageSuitable for US Voltagэлектронная сістэмаMust Connect with Neutral LineРэкамендаваны тавар
One Live Line Voltagе 110В110/230В1 Live line + 1 Neutral lineATS-2P-63A-110V
2 Live line + 1 Neutral lineATS-3P-63A-110V
3 Live line + 1 Neutral lineATS-4P-63A-110V
One Live Line Voltagе 230В220/400В1 Live line + 1 Neutral lineATS-2P-63A-220V
2 Live line + 1 Neutral lineATS-3P-63A-220V
3 Live line + 1 Neutral lineATS-4P-63A-220V

Заўвага: Выпtage of the common and backup power supply must be 85-110% of the rated voltage, and the current cannot be less than 5A, otherwise the coil will heat up or even spontaneously combust. The backup power of the product must be a stable city power, otherwise the product will not switch automatically.

5. Памеры прадукту

The GEYA Mini ATS is designed for compact installation with universal DIN rail mounting. Refer to the diagram below for detailed dimensions.

GEYA Mini ATS Product Dimensions

Figure 6: Product Dimensions (in mm)

  • Агульная даўжыня: 125 мм
  • Агульная шырыня: 78.5 мм
  • Агульная вышыня: 103 мм
  • DIN Rail Mounting Height: 35 мм
  • Safety Distance S1: ≥ 30 мм
  • Safety Distance S2: ≥ 203 мм
Detailed Product Dimensions and Safety Distances

Figure 7: Detailed Dimensions and Safety Clearances

6. Тэхнічныя характарыстыкі

Below are the technical specifications for the GEYA Mini ATS Automatic/Manual Transfer Switch.

GEYA Mini ATS Technical Parameters

Figure 8: Technical Parameter Table

Technical Specifications (Model 3P-63A-110VAC)
ПараметрСпецыфікацыя (63A)Спецыфікацыя (100A)
Rated current Ie A63А100А
Ізаляцыя абtage UiПераменны ток 690 В
Увод абtage UeAC 110V / AC 220V
ГатунакPC grade: able to make and withstand not to break short-circuit current
Выкарыстоўвайце катэгорыюАС-33іБ
паляк2P / 3P / 4P
Вага (кг)0.81-
жыццёElectrical: 2000 times; Mechanical: 5000 times
Rated conditional short circuit current50 кА
SCPD (fuse)РТ16-00-63АРТ16-00-100А
Намінальная ўстойлівасць да імпульсу8кВ
Control circuit (Input voltage: AC 110V)Намінальны кантроль абtage Us: AC110V, 50Hz; Correct working condition 85%-110% Us
Control circuit (Input voltage: AC 230V)Намінальны кантроль абtage Us: AC230V, 50Hz; Correct working condition 85%-110% Us
Частата току50/60 Гц
Contact transfer time<50 мс
Аператыўны час перадачы<50 мс
Return transfer time<50 мс
Off-time-55°C ~ +40°C
Дыяпазон тэмпературAverage temperature not more than 35°C in 24 hours
Main Technical Parameters for W2R-100

Figure 9: Main Technical Parameters for W2R-100 Series

7. Настройка і ўстаноўка

7.1 Ідэнтыфікацыя кампанентаў

Familiarize yourself with the different parts of the transfer switch before proceeding with installation.

GEYA Mini ATS Wiring Instructions - Part Names

Figure 10: Analysis of Each Part Name (3P Poles)

  • Сігнальны тэрмінал: For control signals.
  • Source A Power Inlet Terminal: Connection point for Main Power (Source A).
  • Source A Power Indicator: Indicates status of Source A.
  • Auto/Manual Mode Switch: Selector for operation mode.
  • Source B Power Indicator: Indicates status of Source B.
  • Transfer Handle: Manual override for switching power sources.
  • Source B Power Inlet Terminal: Connection point for Standby Power (Source B).
  • Power Output (Load Port): Connection point for the electrical load.

7.2 Электрычная схема

Follow the wiring diagrams carefully to ensure correct and safe installation. The device supports connection to mains, generator, or photovoltaic systems.

Combination of Photovoltaic and Generator with ATS

Малюнак 11: Выпample of Photovoltaic and Generator Combination Wiring

GEYA Mini ATS Wiring Diagram

Figure 12: General Wiring Diagram (3P Poles)

Product Wiring Diagram Exampлес

Figure 13: Various Product Wiring Diagram Exampлес

Крокі праводкі:

  1. Mount the ATS on a DIN rail in a suitable enclosure.
  2. Connect the Main Power (Source A) to the "Source A Power Inlet Terminal" (AR, AS, AT, AN).
  3. Connect the Standby Power (Source B) to the "Source B Power Inlet Terminal" (BR, BS, BT, BN).
  4. Connect the load to the "Power Output (Load Port)".
  5. Ensure all connections are secure and tightened to prevent loose contacts and overheating.
  6. Connect the control lines (Common Neutral line, Common control line, Alternate control line) as per the diagram for automatic operation.

Video: Wiring Example and Operation Demonstration

Video 1: This video demonstrates the wiring process and basic operation of the GEYA ATS (W2R) unit. It shows how to connect power sources and loads, and how the switch responds to power changes.

8. Інструкцыя па эксплуатацыі

The GEYA Mini ATS can operate in both automatic and manual modes.

8.1 Аўтаматычны рэжым

  • Set the "Auto/Manual Mode Switch" to АЎТА.
  • When normal power supply A is working properly, the A (red light) indicator will be on.
  • If normal power supply A becomes abnormal (e.g., power outage, under/over voltage), the A (green light) indicator will go off, and the switch will automatically transfer the load to backup power supply B.
  • When normal power supply A recovers, the switch will automatically transfer the load back to power supply A.

8.2 Ручны рэжым

  • Set the "Auto/Manual Mode Switch" to КІРАЎНІЦТВА.
  • To select power supply A, manually operate the red transfer handle towards power supply A. The red light for A will turn on.
  • To select power supply B, manually operate the red transfer handle towards power supply B. The red light for B will turn on.
  • In manual mode, the switch will not automatically transfer power.

Video: Automatic/Manual Transfer Switch Operation

Video 2: This video illustrates the functionality of the GEYA Automatic/Manual Transfer Switch (W2R), demonstrating how it switches between power sources.

Video: ATS Usage Demonstration

Video 3: A brief demonstration of the GEYA ATS (W2R) in action, showing the power transfer process.

9. Тэхнічнае абслугоўванне

The GEYA Mini ATS is designed for reliable operation with minimal maintenance. However, periodic checks are recommended to ensure optimal performance and safety.

  • Візуальны агляд: Regularly inspect the switch for any signs of physical damage, loose connections, or discoloration due to overheating.
  • Герметычнасць клем: Periodically check and tighten all terminal screws to ensure good electrical contact.
  • Чысціня: Keep the switch free from dust, dirt, and moisture. Use a dry, soft cloth for cleaning.
  • Праверка функцыянальнасці: Occasionally test the automatic transfer function by temporarily disconnecting the main power source (if safe to do so) to ensure the switch transfers to the backup source as expected.

10. Выпраўленне непаладак

If you encounter issues with your GEYA Mini ATS, consider the following troubleshooting steps:

  • No Power Transfer:
    • Check if both power sources (A and B) are active and within the specified voltage range (85-110% of rated voltagе).
    • Ensure the "Auto/Manual Mode Switch" is set to AUTO for automatic operation.
    • Праверце, ці ўсе злучэнні правадоў надзейныя і правільныя ў адпаведнасці са схемай падключэння.
    • Check if the current is below 5A, which can cause the coil to malfunction.
  • Indicator Lights Not Functioning:
    • Confirm that the corresponding power source is active.
    • Inspect for loose internal connections (requires professional inspection).
  • Перагрэў:
    • Ensure the current is not below 5A.
    • Праверце, ці няма аслабленых клеммных злучэнняў.
    • Verify the load does not exceed the rated current of the switch.

For persistent issues or complex problems, contact qualified electrical personnel or GEYA customer support.

11. Гарантыя і падтрымка

GEYA products are manufactured to high-quality standards. For warranty information and technical support, please refer to the official GEYA webсайт або звярніцеся да мясцовага дыстрыбутара. Захоўвайце чэк аб куплі для прэтэнзій па гарантыі.

Для атрымання дадатковай дапамогі наведайце GEYA Store on Amazon.

© 2023 GEYA. All rights reserved.

Manufacturer: ZHEJIANG GEYA ELECTRICAL CO.,LTD