Diversitech CP-22LPT

Asurity by Diversitech CP-22LPT Low Profile Інструкцыя па эксплуатацыі кандэнсатнага помпы

Model: CP-22LPT

Уводзіны

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your Asurity by Diversitech CP-22LPT Low Profile Condensate Pump. This pump is designed to automatically evacuate condensate or water discharge from HVACR equipment, offering a vertical lift capability of up to 22 feet. Its low-profile design makes it suitable for installations in tight spaces.

Інфармацыя па бяспецы

Read all instructions carefully before installation and operation. Failure to follow these instructions may result in property damage, personal injury, or death.

  • Электрычная небяспека: Disconnect power before servicing. This unit operates on 110 Volts. Ensure all electrical connections comply with local codes.
  • Небяспека для вады: This pump handles water. Ensure proper drainage and prevent water damage.
  • Ўстаноўка: Install the pump in a location where it is accessible for maintenance and inspection.
  • Прызначэнне: Use this pump only for its intended purpose of evacuating condensate from HVACR equipment.
  • У спісе UL: This product is UL listed, meeting electrical and mechanical safety standards for water pumps.

Змест пакета

Перад пачаткам усталёўкі пераканайцеся, што ўсе элементы наяўныя:

  • Asurity by Diversitech CP-22LPT Condensate Pump
  • 20 ft Clear Vinyl Tubing
  • 4 ft Safety Switch Wire (pigtail)

Прадукт скончаныview

The Asurity CP-22LPT condensate pump features a compact design with advanced functionalities for reliable condensate removal.

Asurity CP-22LPT Condensate Pump with Clear Tubing

Малюнак 1: The Asurity CP-22LPT low profile condensate pump shown with the included clear vinyl tubing. The pump features a red base and a black motor housing with ventilation slots and an outlet port.

Asurity CP-22LPT Condensate Pump with Tubing and Safety Switch Wire

Малюнак 2: Зверху ўніз view of the Asurity CP-22LPT condensate pump, accompanied by the coiled clear vinyl tubing and the yellow safety switch wire. This image highlights all primary components included with the unit.

Збоку View of Asurity CP-22LPT Condensate Pump

Малюнак 3: A side perspective of the Asurity CP-22LPT condensate pump, illustrating its low-profile design. This view emphasizes the compact dimensions suitable for installation in confined spaces.

Асноўныя характарыстыкі:

  • LED Status Indicator Lights (Power, Run, Alarm)
  • Вібрацыя Dampening System for quiet operation
  • Integrated Safety Switch with 4 feet of wire for air-handler shutdown
  • Нізкі прафесіяналfile design for tight installations
  • Metal mounting tabs for secure installation
  • Four inlet holes (with 3 poly covers for unused ports)
  • Float switch and duckbill-style check valve

Настройка і ўстаноўка

Proper installation is crucial for the pump's performance and longevity. Ensure all local electrical and plumbing codes are followed.

  1. Размяшчэнне: Position the pump on a level surface near the HVACR unit. The low-profile design is ideal for tight spaces. Utilize the vibration dampening feet and metal mounting tabs for secure placement.
  2. Condensate Inlet Connection: Connect the condensate drain line from the HVACR unit to one of the pump's inlet holes. The pump has four inlet holes; seal any unused inlets with the provided poly covers.
  3. Discharge Line Connection: Connect the 20 ft clear vinyl tubing to the pump's discharge outlet. Route the tubing upwards, ensuring it does not exceed the pump's 22 ft vertical lift capability, and then to a suitable drain point. Avoid kinks or sharp bends in the tubing. The integrated duckbill-style check valve prevents backflow.
  4. Электрычнае падключэнне: Connect the pump to a dedicated 110V power supply. Ensure the power source is off before making connections.
  5. Падключэнне засцерагальнай прылады: Connect the 4 ft safety switch wire (pigtail) to the air-handler's shutdown circuit. This feature is designed to shut down the HVACR unit if the pump fails or the water level rises too high, preventing overflow. Refer to your HVACR unit's manual for specific wiring instructions for the safety switch.
  6. Тэставанне: After installation, manually pour water into the pump's reservoir to verify proper operation. The pump should activate, discharge the water, and then shut off. Check for any leaks.

Інструкцыя па эксплуатацыі

The Asurity CP-22LPT condensate pump operates automatically once properly installed and powered.

  • When condensate water enters the pump's reservoir and reaches a predetermined level, the internal float switch activates the pump.
  • The pump will then discharge the water through the connected vinyl tubing to the designated drain.
  • Once the water level drops, the float switch deactivates the pump.
  • Святлодыёдныя індыкатары:
    • Pwr (Power): Illuminates when the pump is receiving electrical power.
    • запусціць: Illuminates when the pump motor is actively discharging water.
    • Alrm (Alarm): Illuminates if the water level rises to the high-level alarm switch, indicating a potential issue and activating the safety shutdown circuit.

Тэхнічнае абслугоўванне

Рэгулярнае тэхнічнае абслугоўванне забяспечвае аптымальную прадукцыйнасць і падаўжае тэрмін службы вашага кандэнсатнага помпы.

  • Штомесячны агляд: Check the pump reservoir for sludge, mold, or debris. Clean as necessary.
  • Уборка: Disconnect power before cleaning. Remove the pump cover and clean the reservoir with a mild detergent and water. Ensure the float switch moves freely.
  • Выпускная лінія: Inspect the vinyl tubing for blockages, kinks, or leaks. Clear any obstructions.
  • Уваходныя парты: Ensure inlet ports are clear of debris.

Ліквідацыю непаладак

Звярніцеся да наступнай табліцы, каб азнаёміцца ​​з распаўсюджанымі праблемамі і іх рашэннямі.

праблема Магчымая прычына Рашэнне
Помпа не працуе No power; Clogged inlet/outlet; Stuck float switch; Motor failure Check power supply; Clear blockages; Inspect/clean float switch; Contact support if motor fails
Помпа працуе бесперапынна Stuck float switch; Leak in discharge line; Pump undersized for flow rate Inspect/clean float switch; Check for leaks; Verify pump capacity meets demand
Water overflow / Alarm LED on Pump failure; Clogged discharge line; Safety switch activated Check pump operation; Clear discharge line; Investigate cause of high water level
Празмерны шум/вібрацыя Debris in pump; Improper mounting; Worn motor bearings Clean pump; Ensure secure mounting; Contact support for motor issues

Тэхнічныя характарыстыкі

Асаблівасць Дэталь
Марка Diversitech (Asurity)
Нумар мадэлі СР-22ЛПТ
тtage 110 вольт
Крыніца харчавання Правадная электрычная
Максімальны ўздым 22 футы
Максімальны расход 1.6 літра ў хвіліну
Памеры прадукту 12 см Д х 6.75 см Ш х 6 см В
Вага прадмета 5.41 фунта
Матэрыял Пластыкавыя
Колер Чырвоны чорны
Уключаныя кампаненты Condensate Pump, 20ft clear vinyl tubing, 4ft safety switch wire (pigtail)
Сертыфікаты У спісе UL

Гарантыя і падтрымка

For warranty information or technical support, please contact Diversitech customer service. Keep your purchase receipt for warranty claims.

вытворца: Дыверсітэх

Webсайт: www.diversitech.com

Кантакты: Звярніцеся да інструкцыі вытворцы webсайт для атрымання актуальнай кантактнай інфармацыі.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.