1. Уводзіны
The SINOTIMER STVP series automatic over-voltagе і пад-вtage protector is designed for three-phase 3*127V/220VAC power systems with a rated working current of 80A. This device provides essential protection for electrical equipment by instantaneously cutting off the power supply when over-voltagе, пад-абtage, or over-current conditions are detected. Once the circuit voltage returns to normal, the protector automatically restores power, ensuring continuous operation and safeguarding your appliances from damage.
This protector integrates multiple protection functions including over-voltagе, пад-абtage, over-current, three-phase current (voltage) imbalance, phase sequence (reverse phase), zero-break, and phase-break protection. It also features voltmeter and ammeter functions, and the ability to restore factory settings. The device offers comprehensive features, stable performance, and ease of operation.
Падрабязную інструкцыю карыстальніка ў фармаце PDF можна спампаваць: Кіраўніцтва карыстальніка (PDF)
2. Асноўныя магчымасці
- Звышtagе абарона
- Пад-абtagе абарона
- Абарона ад перагрузкі па току
- Аўтаматычнае аднаўленне
- тtage display (separate ABC phase voltagэлектроннае вымярэнне)
- Ampere display (separate ABC phase ampere measurement)
- Трохфазны ampere unbalance protection
- Phase sequence protection (reverse phase protection)
- Zero line break protection
- Абарона ад абрыву фазы
- Fault inquiry function
- Rotation display of voltage and current for each phase
- Adjustable over-voltage protection value and recovery value
- Adjustable under-voltage protection value and recovery value
- Adjustable over-current protection value and action time
- Adjustable 3-phase ampere unbalance protection value and action time
- Adjustable delay time after power-on
- Adjustable fault recovery delay time
- Factory data reset function
3. Тэхнічныя характарыстыкі прадукту
| Атрыбут | Каштоўнасць |
|---|---|
| Нумар мадэлі | STVP936-1-80A |
| Электразабеспячэнне | 3*127V/220VAC 60Hz |
| Намінальны выпtage | 220В |
| Фаза | Трохфазная |
| Макс. Ток нагрузкі | 1~80A Adjustable (default: 80A) |
| ЗвышtagДыяпазон абароны электроннай | 121V-150V-OFF Adjustable (default: 140V) |
| Звышtage Recovery Range | 120V-149V (default: 135V) |
| Звышtage Action Time | 0.1~10 seconds (default: 0.2s) |
| Пад-абtagДыяпазон абароны электроннай | 118V-80V-OFF Adjustable (default: 90V) |
| Пад-абtage Recovery Range | 118V-91V (default: 95V) |
| Пад-абtage Action Time | 0.1~10 seconds (default: 0.2s) |
| 3-Phase Volt Unbalance Protection | 10%~50%~OFF (default: 20%) |
| 3-Phase Volt Unbalance Action Time | 0.1~10 seconds (default: 1s) |
| Delay Time After Power-on | 2~255 seconds (default: 2s) |
| Fault Recovery Delay Time | 2~600 seconds (default: 60s) |
| Мадэль дысплея | ВК |
| Памеры | 71.5mm (W) * 95.2mm (H) * 65.7mm (D) |
| Ўстаноўка | 35-мм DIN-рэйка |
| Атэстацыя | CE, RoHS |
4. Інфармацыя па бяспецы
- Ўстаноўку і тэхнічнае абслугоўванне павінны выконваць толькі кваліфікаваныя электрыкі.
- Перад любымі мантажнымі або электрамантажнымі работамі пераканайцеся, што электрасілкаванне адключана.
- The device does not provide overload or short-circuit protection. It must be used in conjunction with appropriate external circuit breakers (e.g., C45, C65 mini circuit breakers) for comprehensive protection.
- Перад падачай харчавання пераканайцеся, што ўсе злучэнні правадоў надзейныя і правільныя.
- Do not operate the device in wet or hazardous environments.
5. Ўстаноўка
5.1 Фізічныя памеры

5.2 Мантаж
The protector is designed for 35mm DIN rail installation. Snap the device onto the DIN rail securely.

5.3 Электрычная схема
Connect the input and output terminals as shown in the diagram below. Ensure correct phase (L1, L2, L3) and neutral (N) connections. The input terminals are located at the top, and output terminals at the bottom.


6. Налада і канфігурацыя
Каб увайсці ў рэжым налад, націсніце і ўтрымлівайце НАБОР button for 3 seconds. Then, continuously press НАБОР to cycle through the parameters. Use the ▲ і ▼ buttons to adjust the values. When "ENd" appears, press НАБОР again to save the data and exit the setting mode.
If no operation is performed within 10 seconds after pressing НАБОР, the device will automatically exit the setting mode, and any unsaved changes will be lost.
6.1 Parameter Settings Table
| Крок | Змест | ВК-дысплей | Description / Range (Default) |
|---|---|---|---|
| 1 | ЗвышtagЗначэнне абароны | Uvo 280V | 221V-300V-OFF (280V) |
| 2 | Звышtagе значэнне аднаўлення | Uvor 250V | 220В-299В (250В) |
| 3 | Звышtagчас дзеяння электроннай абароны | 0.2S | 0.1-10 с (0.2 с) |
| 4 | Пад-абtagЗначэнне абароны | Uve 160V | 219V-150V-OFF (160V) |
| 5 | Пад-абtagе значэнне аднаўлення | Uver 180V | 151В-220В (180В) |
| 6 | Пад-абtagчас дзеяння электроннай абароны | 0.2S | 0.1-10 с (0.2 с) |
| 7 | Значэнне абароны ад перагрузкі па току | >In 80A | 1-80A (80A) |
| 8 | Over-current protection action time | 5S | 1-512 с (5 с) |
| 9 | 3 фаз amp unbalance protection value | >In % | 5%-90%-OFF (25%). Not active if current < 2A. |
| 10 | 3 фаз amp unbalance protection action time | 1.0 С | 0.1-10 с (1 с) |
| 11 | Абарона паслядоўнасці фаз | ON ABC | ON or OFF (ON) |
| 12 | Час затрымкі ўключэння | 2 С | 2-255 с (2 с) |
| 13 | Fault recovery delay time | 60 С | 2-512 с (60 с) |
| 14 | Fault inquiry code | E0 | Press ▲ to view last 5 fault records (E1-E5). >U for overvoltage, <U for undervoltage. |
| 15 | Заканчэнне | КАНЕЦ | Press SET to save and exit. |
6.2 Скід да заводскіх налад
To reset the device to factory settings, press and hold the ▲ і ▼ кнопкі адначасова на працягу 3 секунд.
7. Аперацыя
Once installed and configured, the device will continuously monitor the three-phase power supply. The LCD screen will automatically rotate to display the real-time voltage and current for each phase (L1, L2, L3).
У выпадку завышэння аб'ёмуtagе, пад-абtage, or over-current event, the protector will automatically trip and cut off the power supply to protect connected equipment. After the fault condition clears and the recovery delay time has passed, the device will automatically restore power.
8. Выпраўленне непаладак
8.1 Fault Inquiry
If a fault occurs, the device will display an error code (E0). You can press the ▲ button to query the last 5 fault records (E1-E5). The display will indicate:
- ">U" for overvoltagе падзеі.
- "<U" for undervoltagе падзеі.
8.2 Phase Sequence Error
If the LCD displays "ABC" character, it indicates a phase sequence error. To correct this, arbitrarily reverse any two of the three phase lines (L1, L2, L3) at the input.
9. Тэхнічнае абслугоўванне
- Трымайце прыладу ў чысціні і без пылу і вільгаці.
- Regularly check wiring connections for tightness and signs of wear or damage.
- Do not attempt to repair the device yourself. Refer to qualified personnel for service.
10. Гарантыя і падтрымка
For technical support, inquiries, or warranty claims, please contact the distributor:
Дыстрыб'ютар: XNY INTERNATIONAL LIMITED
Адрас: Room 20A, Kiu Fu Commercial Building, 300 Lockhart Road, Wanchai, Hong Kong.
тэл.: 0086 57761733853
Факс: 0086 577 89736991
WhatsApp: 0086 1565857 3377
WeChat: sinotimer
Skype: sinotimer
Web: www.sinotimer.com
электронная пошта: info@sinotimer.com