Інструкцыя па эксплуатацыі праграмуемага індыкатара працэсу Contrec 150A

Contrec 150A Programmable Process Indicator

Contrec 150A Programmable Process Indicator

Contrec 150A Programmable Process Indicator

УВОДЗІНЫ

The Model 150 Process Indicator is a microprocessor based instrument which accepts a 4-20mA input and displays the input signal and the process variable on a large LCD display. It is powered entirely from the 4-20mA loop and, therefore, does not require an external power source.

The input is displayed on a bar graph as 0…100%. The process variable is a 7 digit numeric display which can be spanned in any engineering units.

The instrument is fully programmable; the user can program alarm settings, span & zero and non-linear correction points. Calculation constants are also set from the front panel and are stored in a non-volatile memory which retains data indefinitely.

The Model 150 Process Indicator conforms conforms to the EMC-Directive of the Council of European Communities 2014/30/EU, the LVD directive 2014/35/EU and the following standards

EN61326:2013: Электрычнае абсталяванне для вымярэння, кантролю і лабараторнага выкарыстання – патрабаванні да электрамагнітнай суміснасці: жылыя памяшканні, камерцыйныя ўмовы і асяроддзе лёгкай прамысловасці і прамысловае асяроддзе.

EN61010:2010: Патрабаванні бяспекі да электраабсталявання для вымярэння, кантролю і лабараторнага выкарыстання.

In order to comply with these standards, the wiring instructions in Section WIRING must be adhered to.

СПЕЦЫФІКАЦЫЯ

Генерал

Дысплей: Continuously powered LCD.
узровень: 30mm bar graph.
Level Span: 0…100% per full scale.
Працэс: 7 digit with 4½ digit resolution, 12mm (0.5″) high.
Process Span: The units of measure (eg. pressure) at full scale of input signal. The span is programmable in the range of 0.000…9,999,999.
Дзесятковыя кропкі: Decimal point positions for the process variable is programmable in range of 0…3 decimal points.
Тып сігналу: 4-20 мА.

4-20 мА

Разрозненне і лінейнасць: 0.05% дыяпазону.
Дакладнасць: 0.05% of span @ 25°C. 0.1% (typically) of span full temperature range.
Час абнаўлення: 0.5 секунда.
падключэнне: 2 wire.
тtage Drop: 2.5В максімум.

Выхады

Тып: 4 open collector output alarms suitable for driving dc solenoids or external relays. The outputs provide:

  1. High-high.
  2. Высокі.
  3. Нізкі.
  4. Low-low.

Магутнасць пераключэння: 200mA. 30Vdc maximum.
Насычэнне Voltage: 0.8Vdc across the output in the “on” state.
Ізаляцыя: All outputs are separately opto-isolated.

фізічны

Працоўная тэмпература: -20°C да 60°C.
Памеры: 97mm (3.8″) high x 150mm (5.9″) wide x 41mm (1.6″) deep (not including cable glands).
Абарона: Nema 4X or IP67 standards.
Кабель Уваход: Кабельныя ўводы.
Мантаж: Universal mounting bracket is supplied as standard.
Мантаж трубы: A galvanised metal bracket is available which enables the instrument to be mounted on a 2″ horizontal or vertical pipe.

АПЕРАЦЫЯ

The Model 150 Process Indicator accepts a 4-20mA input signal from a sensor such as a pressure transmitter, temperature sensor or load cell transmitter. The instrument is powered entirely from the loop and, therefore, requires no external power or internal batteries.

The instrument is fully programmable with all operating parameters and calculation constants programmable from the front panel (see Section PROGRAM STEPS). The setup parameters are stored in a non-volatile memory and are retained indefinitely in the event of a power loss.

ДЫСПЛЕЙ

The display of the Model 150 comprises of: 

Process Signal Bar Graph
Process Variable Numeric Display

Signal Bar Graph

The signal bar graph displays the input signal as a percentage.

Inputs of 4mA and 20mA can be programmed to correspond to 0% and 100% respectively, or can be inverted so that 4mA will correspond to 100% and 20mA will correspond to 0%.

Signal Bar Graph

Пераменная працэсу

The process variable is a 7 digit numeric display which can be spanned, during setup, to read in any engineering units. The process variable is displayed with 4½ resolution in respect to the maximum reading.

Напрыкладample, if the maximum reading is 1234567, the display will show up to 5 digits plus trailing zeros. At different inputs the following will be displayed:

1234567 will be displayed as 1234500; 234567 will be displayed as 234500.

However, if the first digit is greater than 1, then up to 4 digits only will be displayed with trailing zeros. For example, if the maximum contents is 2345678, then at different inputs:

2345678 will be displayed as 2345000; 345678 will be displayed as 345000.

CALCULATION OF THE PROCESS VARIABLE 

For a linear signal/process variable relationship, the contents is calculated as follows:

Process Variable = (Span) x (% Signal) + Offset

where the Span and Offset are constants programmed during programming

РАБОТА ПЯРДНЯЙ ПАНЕЛІ

Адлюстраванне даных

The alarm set points can be viewed by pressing the DISPLAY key.

Адлюстраванне даных

Changing Data

Each of the above parameters can be changed as follows:

  1. Pressing the DISPLAY key consecutively until the numeric value of the parameter to be changed appears (as described in the previous diagram).
  2. This value can then be changed using the following keys:
    Значок This key steps from digit to digit, causing the digit to flash. Only flashing digits can be changed.Значок This key increments the flashing digit.

Exampле. 

To change the high alarm setpoint to 75:

  1. Press DISPLAY until the value of the high alarm appears. This will be the value after AL-HI.
  2. The first digit is flashing, this means it can be changed. Using the Значок key, this digit is changed to 7.
  3. The Значок key is pressed so that the second digit flashes.
  4. Выкарыстоўваючы Значок key, this digit is changed to 5.

Note that the Model 150 can be programmed so that the above parameters cannot be changed, see Section PROGRAM STEPS.

Timeout Condition

Upon entering the display mode, if no key is pressed for 10 seconds, the display returns to the process variable display with alarm acknowledgment cleared.

РЭЖЫМ ТЭСТУ

The 150 has a test mode which can be entered by simultaneously pressing all 3 front panel keys. There are 3 tests:

Low Test: Націснуўшы Значок key, the low and low-low alarms outputs will be energised.

High Test: Націснуўшы Значок key, the high and high-high alarm outputs will be energised.

Тэст дысплея: By pressing the DISPLAY key, all segments of the display will flash.

To exit the test mode all three keys are pressed simultaneously.

сігналізацыі

The Model 150 has 4 alarm outputs:

  • Сігнал
    Сігнал

The alarms can be assigned to signal or process variable which is done during programming (see Section PROGRAM STEPS). Each alarm is individually programmed as a percentage (0-100%) of signal or process variable.

All of the alarms have open collector outputs and are separately isolated via opto-isolators. The outputs are internally protected against voltage скокі, выкліканыя рэле і шпулькамі.

Тыпы сігналізацый

Выхад сігналізацыі

The Model 150 can be programmed for the alarm outputs to operate in one of two ways:

  1. The alarm outputs can energise (switch on) during an alarm condition, or;
  2. The alarm outputs can de-energise (switch off) during an alarm condition.

High Alarms

The high alarms will be activated when the signal or process variable increase above the high alarm setpoints. These alarms will be deactivated when the value falls below these programmed setpoints.

When setting the alarms, the high-high alarm should be set higher than the high alarm.

Low Alarms

The low alarms will be activated when the signal or process variable falls below the low alarm setpoints. These alarms will be deactivated when the value exceeds the programmed setpoint.

Similarly, when setting the low alarms, the low-low alarm should be set below the low alarm.

Alarm Dead band

To prevent an alarm toggling on and off when the signal is close to the setpoint, a user programmable deadband is provided. The deadband is a percentage (0-100%) of the maximum signal or process variable.

Exampтолькі 1. 

If the low alarm is set to 20% and the deadband is set to 5%, the alarm will be activated when the value reaches 20%. The alarm will then stay activated until the value increases above 25%.

Exampтолькі 2. 

If the high alarm and deadband are set at 80% and 5% respectively, the alarm will be activated at 80% and will stay activated until the value falls below 75

Дзеянне сігналізацыі

When an alarm condition exists the Model 150 will act in the following way:

  1. The appropriate alarm output will be activated.
  2. The display will flash the name of the alarm.
  3. In some cases these alarms may be acknowledged from the front panel. This will depend on whether they are programmed as continuous or acknowledgeable alarms. This is set up during programming (see Section PROGRAM STEPS).

The differences between acknowledging continuous and acknowledgeable alarms are described in the table below.

Acknowledgeable Alarms

  1. These alarms are acknowledged by pressing the DISPLAY key.
  2. Once the alarm is acknowledged the flashing on the LCD will cease, with the alarm message remaining solid. The message will remain on the screen until the alarm condition no longer exists.
  3. Once the alarm is acknowledged, the alarm output will be deactivated.

Continuous Alarms

  1. A continuous alarm cannot be acknowledged.
  2. The flashing on the LCD cannot be stopped and will keep flashing until the alarm condition no longer exists.
  3. The alarms will only be deactivated when the signal (or process variable) is outside alarm conditions.

Заўвага: Note that acknowledging the LL alarm will also acknowledge (and deactivate) the L alarm. Similarly, acknowledging the HH alarm will also acknowledge (and deactivate) the H alarm.

Ўстаноўка будзільнікаў

To set any of the alarms:

  1. Press the DISPLAY key until the name of the alarm to be changed appears (see Section Displaying Data).
  2. Выкарыстоўвайце Значок і Значок keys to change the value of the alarm.
  3. Press the DISPLAY key until the original screen appears.

NON-LINEARITY

The Model 150 can be programmed to correct for the non-linearities between the signal input and the process variable.

A correction table, which corrects for non-linearities, can be programmed during setup. This table works as follows:

Нелінейнасць

DETERMINING THE NON-LINEAR CORRECTION TABLE 

Exampле. 

A spherical tank has a diameter of 10m. The tank has a pressure transmitter mounted at the base of the tank which records the head of liquid in the tank. The pressure transmitter zero is set at 5kPa and the span is 100kPa. The following 15 point relationship has been determined:

Увод Process Variabl (Volume) Normalised Inputs for Table
Pressure kPa Pressure Transmitter Output m3 Увод Выхад
5.00 4 мА 3.796 0.000 0.000
1 10.94 17.421 0.0625 0.026
2 16.88 39.699 0.125 0.069
3 22.81 69.314 0.188 0.126
4 28.75 104.951 0.150 0.195
5 34.69 145.295 0.313 0.272
6 40.63 189.031 0.375 0.356
7 46.56 234.844 0.438 0.444
8 52.50 281.418 0.500 0.534
9 58.44 327.438 0.563 0.623
10 64.38 371.590 0.625 0.708
11 70.31 412.557 0.688 0.786
12 76.25 449.025 0.750 0.857
13 82.19 479.678 0.813 0.916
14 88.13 503.202 0.875 0.961
15 94.06 518.280 0.937 0.990
100.00 20 мА 523.599 1.000 1.000

Дзе,

Матэматычная формула

Так, напрыкладample, at 94.06kPa the normalized input is:

Матэматычная формула

Сапраўды гэтак жа

Матэматычная формула

If the Zero is > 0

Так, напрыкладample, at 94.06kPa the volume is 518.280m3 and the normalized output is:

Матэматычная формула

SELECTING THE NUMBER OF POINTS FOR NON-LINEAR CORRECTION

The user can program up to 25 points. However, the values at 4mA or 20mA which are set at 0 and 1 respectively, are not programmed. It is not always necessary to program all 25 points, as it will depend on the shape of the tank.

ФІЛЬТРАВАННЕ

Input fluctuations in the signal can interfere with the stability of the signal and process variable readings. For this reason, the Model 150 has a digital filter which will average out these fluctuations and enable accurate readings.

The degree of filtering of the input signal can be adjusted, depending on the amount of fluctuation and the particular application. Values from 1 to 99 can be programmed, where 1 corresponds to no filtering and 99 corresponds to heavy filtering. Such flexibility in filtering means that highly accurate and stable readings can be obtained.

When programming the degree of filtering, it is advisable to start with no filtering (the factor equals 1) and gradually increase until a steady reading is obtained. It is important that the filtering is not too heavy because this will cause an overdamped response.

The graph on the following page shows the time to reach 90% and 99% of a new reading for a step change in input signal.

Filter Factor vs Time to Reach New Reading
(for a step change in input signal) 

Аперацыя

ПРАГРАМІРАВАННЕ

The Model 150 is fully programmable with all parameters being stored in memory.

Каб увайсці ў рэжым праграмы: 

Remove the lower cover strip (the dark grey strip along the bottom of the front of the enclosure) and replace it the reverse side up. This brings a small magnet on the inside of the cover strip in contact with a reed switch inside the instrument. The word “Set” is then displayed.

To exit Program Mode: 

The grey strip should be replaced the correct way up.

The key switch actions are as follows:

Значок This key steps from digit to digit, causing the digit to flash.

Значок This key will increment a flashing digit or change a parameter selection.

Значок This key will step through the program sequence.

In stepping through the program sequence (using the DISPLAY key), the parameter description is displayed first, followed by the actual value or parameter. When a value or parameter can be changed it is shown as flashing.

КРОКІ ПРАГРАМЫ

Крок Дысплей Апісанне
1 НАБОР Select whether alarms are assigned to the signal or process variable.
сігнал Alarms are assigned to signal.
Прац Alarms are assigned to process variable.
2 ТЫП Select whether alarms are normally energised or normally de-energised.
NE Normally energised.
ND Normally de-energised.
3 ДЗЕЙНІЧАЙЦЕ Select type of alarm action, either continuous on alarm condition or cancels when alarm is acknowledged.
N-AC Continuous on alarm condition.
AC Acknowledged and cancelled with display key.
4 DBAND Alarm deadband.
хх.хх Program alarm deadband as a % of maximum signal or process variable.
5 ФІЛЬТ The filter constant for filtering the input signal.
1 да 99 No filtering.
Very heavy filtering.
6 УВОД Select input type; either inverted or noninverted.
N-INV Non-inverted (zero at 4mA).
ІНВ Inverted (zero at 20mA).
7 ДЫСП Select enable or disable. This will allow (enable) or not allow (disable) the user to change the alarm setpoints from the DISPLAY key.
En Enable the changing of alarm setpoints.
дыс Disable changing alarm setpoints.
8 АДЗІНКА Pressure, Contents, Volume, Rate or (blank) is displayed on the LCD above the process variable.
9 P-DEC The position of the decimal point for the process variable. The user can select 0, 1, 2, or 3 decimal places.
10 P-SPAN Span of the process variable. The span can be programmed in the range of 0.000 to 9,999,999.
11 П-00
12 ЛІН Select whether the input signal is linear or nonlinear.
Лін Лінейны.
N-lin Non-linear.
Steps 13-17 are displayed only if the input signal is non-linear.
13 No-PTS The number of points for non-linear correction. The user can program up to 25 points. Note the user does not program the values at 4mA or 20mA, which are set at 0 and 1 respectively.
14 ІНП-01 Non-linear correction Input Point #01. The input point for the first non-linear correction point is programmed in the range of 0.000 to 0.999. Input points must be programmed in ascending order.
15 ВЫХОД-01 The corresponding Output Point #01 for nonlinear correction is programmed in the range of 0.000 to 0.999.
16 INP-XXX Non-linear correction Input Point #XX. Subsequent input points are programmed in the range of 0.000 to 0.999.
17 OUT-XXX The corresponding Output Point #XX. The corresponding output points are programmed.
18 МЯККІ The software version used in the Model 150 is displayed.

УВОД СІГНАЛА

The signal input is on terminals 3 and 4 and is connected as follows:

  • Ўваходны сігнал
    Ўваходны сігнал

ВЫХОДЫ ТРЫВОГІ

Open collector outputs are provided for high and low level alarms. The output can sink up to 200mA and can be used to power external relays, lights or audible alarms. The outputs are internally protected against voltagе шыпы.

Both outputs are separately isolated via opto-isolators.

Alarm Output Specifications 

Максімальны ток (ракавіна): 200мА.
Максімальны аб'ёмtage: 30 В пастаяннага току.
Насычанасць тtage: 0.8Vdc across outputs in energised state.
Ізаляцыя: All outputs are separately isolated via opto-isolators.

Сувязі

  • Рэле сігналізацыі
    Сувязі
  • Alarm Output to External Circuit
    Сувязі

УСТАНОВКА

НАСЦЕННЫ МАНТАЖ

A wall mounting bracket is supplied with each instrument. Round head screws should be used to attach the bracket to the wall (countersunk screws should not be used). The bracket is mounted first, with the tray section at the bottom. The instrument is then mounted on the bracket with two screws as shown below.

Насценны мантаж

ЗНЯЦЬ ПЕРЕДНЮЮ ПАНЕЛЬ 

Пярэдняя панэль здымаецца наступным чынам:

  1. Remove the top and bottom cover strips (ie. the dark plastic strip) by levering a screwdriver under one end.
  2. Undo the screws retaining the front. Do not remove the screws, they are retained by O-rings.
  3. Remove the front panel from the housing.

Каб замяніць пярэднюю крышку, выканайце апісаную вышэй працэдуру ў зваротным парадку. Перш чым закручваць шрубы, пераканайцеся, што пярэдняя панэль выраўнавана ў месцах злучэння.

Зняцце пярэдняй панэлі

АСНОЎНАЯ ЭЛЕКТРОНІКА 

The front section of the housing contains the microprocessor and display. It is possible to adjust the display contrast via a small potentiometer on the board. The display contrast is shown below and this can be adjusted for optimum contrast.

Adjacent to this control is a reset switch, which can be used to reset the microprocessor. Note that pressing this button will reset all setup parameters.

The Main Electronics

ПРАВОДКА

When connecting the Model 150, it is good practice to use shielded cable. The shield should be connected to earth at one end of the cable. The other end of the shield should not be connected.

This wiring practice is mandatory in order to comply with the requirements for Electromagnetic Compatibility as per EMC-Directive 2014/30/EU of the Council of the European Community.

All printed circuit boards must be repaired by Contre Ltd.

Абазначэння тэрміналаў

Уваход 4-20 мА

3 4-20 мА (-)
4 4-20 мА (+)

Выхады

1 Low-low Alarm (-)
2 Low-low Alarm (+)

5 Нізкі сігнал (-)
6 Нізкі сігнал трывогі (+)

7 High Alarm (-)
8 High Alarm (+)

10 High-high Alarm (-)
11 High-high Alarm (+)

УТЫЛІЗАЦЫЯ

УТЫЛІЗАЦЫЯ ІНСТРУМЕНТА

Прыборы Contrec нельга выкідваць у агульную сістэму смецця.

Сімвал Калі гэты прыбор знаходзіцца ў краінах-членах ЕС, ён павінен быць утылізаваны ў адпаведнасці з рэкамендацыямі WEEE (адходы электрычнага і электроннага абсталявання) 2012/19/EU. Калі гэтае абсталяванне знаходзіцца за межамі ЕС, яго неабходна ўтылізаваць з усёй адказнасцю ў адпаведнасці з мясцовымі і нацыянальнымі правіламі для EEE (электрычнае і электроннае абсталяванне).

Не выкідваючы гэты прадукт разам з іншым хатнім смеццем, вы захоўваеце прыродныя рэсурсы і памяншаеце колькасць адходаў, якія адпраўляюцца на сметнік і ў заводы па спальванні.

Дакументы / Рэсурсы

PDF thumbnail150A Programmable Process Indicator
Instruction Manual · 150A Programmable Process Indicator, 150A, Programmable Process Indicator, Process Indicator, Indicator

Задайце пытанне

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

Задайце пытанне

Ask about setup, compatibility, troubleshooting, or anything missing from this manual. Name and email are optional.